Raritan PX3-5085U-N2 power distribution unit (PDU) 48 AC outlet(s) 0U Black

Raritan PX3-5085U-N2. PDU types: Monitored, Switched, Rack capacity: 0U, Type: Three-phase. AC outlets quantity: 48 AC outlet(s), AC outlet types: C13 coupler, C19 coupler, Power plug: IEC 320. Cable length: 118.1" (3 m). Monitoring: Humidity, Temperature. Nominal input voltage: 400 V, Maximum current: 30 A, AC input frequency: 50 - 60 Hz
Manufacturer: Raritan
Availability: Out of Stock - on backorder and will be dispatched once in stock.
SKU: 6297913
Manufacturer part number: PX3-5085U-N2
$3,167.00
Monitored and switched rack power distribution unit (0U [vertical], 16.6kVA, 48 outlets). INPUT: 400v (3-phase WYE), 30a - NEMA L22-30P plug (4P5W); OUTPUT: 36@ C13, 12@ C19 outlets; on 6@ 1-pole, 20a Overcurrent Protectors; FEATURES: Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet; Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3. Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM. Cascading upto 16 PDU's using single Ethernet or USB connection. Environmental monitoring [temp/humidity] capable – up to 32 sensors. Individual outlet numbers labeled on chassis. Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. WiFi Capable. USB Webcam Capable. iPad/iPhone/Android App. Dual 10/100/1000 Ethernet port. Tri-color status LED per receptacle. Breaker metering and alarming (0V detection). Max Dimensions 52mm x 65mm x 2180mm (2.1in x 2.6in x 85.8in). Max Weight TBD. Maximum ambient temperature 60C at full load.

 

  • Securelock
  • Removable Controller
  • Compatible: Sensors Temperature, Humidity, Air Flow, Differential Pressure, Water, Leak, and Contact Closure
  • Networking: Gigabit (10/100/1000 BaseT) Ethernet port; secondary, redundant (10/100/1000 BaseT) Ethernet port. Optional WiFi (802.11a/b/g/n)
Monitored and switched rack power distribution unit (0U [vertical], 16.6kVA, 48 outlets). INPUT: 400v (3-phase WYE), 30a - NEMA L22-30P plug (4P5W); OUTPUT: 36@ C13, 12@ C19 outlets; on 6@ 1-pole, 20a Overcurrent Protectors; FEATURES: Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet; Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3. Onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM. Cascading upto 16 PDU's using single Ethernet or USB connection. Environmental monitoring [temp/humidity] capable – up to 32 sensors. Individual outlet numbers labeled on chassis. Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. WiFi Capable. USB Webcam Capable. iPad/iPhone/Android App. Dual 10/100/1000 Ethernet port. Tri-color status LED per receptacle. Breaker metering and alarming (0V detection). Max Dimensions 52mm x 65mm x 2180mm (2.1in x 2.6in x 85.8in). Max Weight TBD. Maximum ambient temperature 60C at full load.

 

  • Securelock
  • Removable Controller
  • Compatible: Sensors Temperature, Humidity, Air Flow, Differential Pressure, Water, Leak, and Contact Closure
  • Networking: Gigabit (10/100/1000 BaseT) Ethernet port; secondary, redundant (10/100/1000 BaseT) Ethernet port. Optional WiFi (802.11a/b/g/n)
Products specifications
Attribute nameAttribute value
Height85.8"
MonitoringHumidity, Temperature
Block 1 output current12 A
Block 2 output current16 A
Width2.05"
Depth2.56"
MountingVertical
DisplayLCD
Cable Length118.1"
TypeThree-phase
Technical details
Product colorBlack
Ports & interfaces
Power plugIEC 320
AC outlets quantity48 AC outlet(s)
AC outlet typesC13 coupler, C19 coupler
Ethernet LAN (RJ-45) ports2
USB ports quantity3
Design
PDU typesMonitored, Switched
Operational conditions
Operating altitude0 - 21944.9"
Storage relative humidity (H-H)0 - 100 %
Operating temperature (T-T)0 - 60 °C
Storage temperature (T-T)-25 - 65 °C
Operating relative humidity (H-H)0 - 85 %
Non-operating altitude0 - 120000"
Power
Nominal input voltage400 V
Maximum current30 A
AC input frequency50 - 60 Hz
Power protection featuresOverload
Features
Output voltage208 - 240 V
Rack capacity0U
Other features
Nominal output voltage208 V